Silicone Cold Shrink Wrap And Kits
- Power Frequency Withstand Voltage:
- 39 kV, 5 min, no breakdown
- Partial Discharge Test:
- Partial Discharge Magnitude≤ 10 pC at 15 kV
- Impulse Voltage Test:
- 95 kV, 10 positive and 10 negative impulses, no breakdown
- Constant Voltage Load Cycling Test (in Air):
- 23 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
- Thermal Stability Test (185 mm² Conductor):
- 23.4 kA, 2 s, twice, no visible damage
- Dynamic Stability Test:
- 82.6 kA, ≥ 10 ms, no visible damage
- Moisture Test (Indoor):
- 11 kV, 300 h, no breakdown, no flashover
- Salt Spray Test (Outdoor):
- 11 kV, 1000 h, no breakdown, no flashover
Reliable insulation remains mandatory for medium-voltage power distribution networks. Hangda delivers high-grade Cold Shrink Cable Accessories manufactured with liquid silicone rubber to prevent moisture ingress, electrical tracking, and flashover failures across harsh environments.
Cable Sealing Performance Features
-
Constant Radial Pressure: Active compression ensures tight seals during thermal expansion and contraction cycles.
-
Hydrophobic Surface: Premium silicone shrink wrap rejects water accumulation and reduces surface discharge risks.
-
High Dielectric Strength: Superior breakdown voltage properties safeguard 8.7/15kV cable terminations and splices.
Technical Specifications
| Parameter | Specification | Standard |
|---|---|---|
| Voltage Rating | 8.7/15 kV | IEC 60502-4 |
| Tensile Strength | ≥ 8.5 MPa | ISO 37 |
| Dielectric Strength | ≥ 22 kV/mm | IEC 60243 |
| Operating Temperature | -40°C to +130°C | IEC 60068 |
| Ingress Protection | IP68 | IEC 60529 |
Installation Advantages
Pre-expanded design on removable spiral cores enables rapid tool-free field deployment. Hangda cold shrink kits eliminate open flames, torch permits, and thermal stress on conductor insulation.
Operational Reliability
-
Built-In Stress Control: Integrated geometric field grading minimizes high electric stress at insulation shield cuts.
-
Environmental Resistance: Exceptional UV resistance, ozone durability, and tear strength guarantee continuous service life.
8.7/15 kV Fully Cold Shrink Three-Core Terminal – Installation Outline Drawing

Electrical Performance Tests
| No. | Test Item | Standard Requirements |
| 1 | Power Frequency Withstand Voltage | 39 kV, 5 min, no breakdown |
| 2 | Partial Discharge Test | Partial Discharge Magnitude≤ 10 pC at 15 kV |
| 3 | Impulse Voltage Test | 95 kV, 10 positive and 10 negative impulses, no breakdown |
| 4 | Constant Voltage Load Cycling Test (in Air) | 23 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover |
| 5 | Thermal Stability Test (185 mm² Conductor) | 23.4 kA, 2 s, twice, no visible damage |
| 6 | Dynamic Stability Test | 82.6 kA, ≥ 10 ms, no visible damage |
| 7 | Moisture Test (Indoor) | 11 kV, 300 h, no breakdown, no flashover |
| 8 | Salt Spray Test (Outdoor) | 11 kV, 1000 h, no breakdown, no flashover |
Product overview
◆The product is available in single-core, two-core, three-core, four-core, and five-core versions, and has been widely used for low-voltage cable terminations and intermediate connections.
◆Excellent surface hydrophobicity, ensuring the product maintains strong resistance to contamination.
◆Compact size, lightweight, and reliable performance.
◆Application Scope: The product demonstrates excellent cold and heat resistance, making it particularly suitable for high-altitude, cold, humid, salt-spray, and heavily polluted environments.
Installation requires no open flame, making it ideal for flammable and explosive areas such as petroleum, chemical, mining, and tunneling sites.
![]() |
![]() |
![]() |
![]() |
| 8.7/15 kV Single-Core Cold Shrink Indoor Termination – Installation Drawing | 8.7/15 kV Three-Core Cold Shrink Outdoor Termination – Installation Drawing | 8.7/15 kV Three-Core Cold Shrink Outdoor Termination – Supporting Drawing | 8.7/15 kV Three-Core Cold Shrink Joint – Supporting Drawing |
Technical Data - Model Selection
| Product Type | Model | Conductor Cross-section(mm²) | Product Type | Model | Conductor Cross-section(mm²) | |||
| 8.7/15 kV Three core cold shrink indoor terminal | GHD-15HNLS-3*25-50 | 25-50 | 8.7/15 kV Single core cold shrink indoor terminal | GHD-15HNLS-1*25-50 | 25-50 | |||
| GHD-15HNLS-3*70-120 | 70-120 | GHD-15HNLS-1*70-120 | 70-120 | |||||
| GHD-15HNLS-3*150-240 | 150-240 | GHD-15HNLS-1*150-240 | 150-240 | |||||
| GHD-15HNLS-3*300-400 | 300-400 | GHD-15HNLS-1*300-400 | 300-400 | |||||
| 8.7/15 kV Three core cold shrink outdoor terminal | GHD-15HWLS-3*25-50 | 25-50 | 8.7/15 kV Single core cold shrink outdoor terminal | GHD-15HWLS-1*25-50 | 25-50 | |||
| GHD-15HWLS-3*70-120 | 70-120 | GHD-15HWLS-1*70-120 | 70-120 | |||||
| GHD-15HWLS-3*150-240 | 150-240 | GHD-15HWLS-1*150-240 | 150-240 | |||||
| GHD-15HWLS-3*300-400 | 300-400 | GHD-15HWLS-1*300-400 | 300-400 | |||||
| 8.7/15 kV Three core cold shrink intermediate joint | GHD-15JTLS-3*25-50 | 25-50 | 8.7/15 kV Single core cold shrinkintermediate joint | GHD-15JTLS-1*25-50 | 25-50 | |||
| GHD-15JTLS-3*70-120 | 70-120 | GHD-15JTLS-1*70-120 | 70-120 | |||||
| GHD-15JTLS-3*150-240 | 150-240 | GHD-15JTLS-1*150-240 | 150-240 | |||||
| GHD-15JTLS-3*300-400 | 300-400 | GHD-15JTLS-1*300-400 | 300-400 | |||||