Cold Shrink Tube Price Cable Joints And Terminations
- Power Frequency Withstand Voltage:
- 54 kV, 5 min, No Breakdown
- Partial Discharge Test:
- Partial Discharge Magnitude≤ 10 pC at 20 kV
- Impulse Voltage Test:
- 125 kV, 10 positive and 10 negative impulses, no breakdown
- Constant Voltage Load Cycling Test (in Air):
- 35 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
- Thermal Stability Test (185 mm² Conductor):
- 23.4 kA, 2 s, twice, no visible damage
- Dynamic Stability Test:
- 82.6 kA, ≥ 10 ms, no visible damage
- Moisture Test (Indoor):
- 15 kV, 300 h, no breakdown, no flashover
- Salt Spray Test (Outdoor):
- 15 kV, 1000 h, no breakdown, no flashover
Determining an accurate cold shrink tube price requires analyzing material quality and voltage specifications. Hangdaele manufactures reliable components designed for high-voltage power networks, ensuring stable energy transmission across demanding environments.
Evaluating Cold Shrink Cable Accessories
Proper selection involves assessing the silicone rubber compound used in cold shrinkable cable joints. These components must withstand extreme weather and harsh industrial settings without degrading.
Performance Factors for a Cold Shrinkable Joint
A resilient connection minimizes ongoing maintenance. Hangdaele integrates superior stress control mechanisms to prevent electrical breakdown at the connection point. When evaluating any cold shrinkable termination, specific technical traits stand out:
-
High dielectric strength to prevent partial discharge events.
-
Constant active radial pressure for permanent moisture sealing.
-
Superior tracking resistance for exposed outdoor deployment.
Specification and Investment Analysis
Balancing initial investment with operational lifespan dictates purchasing decisions. Securing favorable rates involves sourcing globally tested components directly from specialized manufacturers.
| Parameter Property | Standard Value Range |
|---|---|
| Voltage Class | 12/20kV to 18/20kV |
| Material Composition | Liquid Silicone Rubber |
| Operating Temperature | -50°C to +90°C |
| Max Expansion Ratio | Up to 2.5 times |
Installation Workflow
Reliable grid operation relies on precise field execution. The application process for Cold Shrink Cable Accessories requires zero heat or specialized tools:
-
Prepare the conductor and strip the semiconductive shielding layer accurately.
-
Position the main insulating body exactly over the connection area.
-
Unwind the inner plastic spiral core counterclockwise to complete the tight seal.
12/20, 18/20 kV Fully Cold Shrink Three-Core Terminal – Installation Outline Drawing

Electrical Performance Tests
| No. | Test Item | Standard Requirements |
| 1 | Power Frequency Withstand Voltage | 54 kV, 5 min, No Breakdown |
| 2 | Partial Discharge Test | Partial Discharge Magnitude≤ 10 pC at 20 kV |
| 3 | Impulse Voltage Test | 125 kV, 10 positive and 10 negative impulses, no breakdown |
| 4 | Constant Voltage Load Cycling Test (in Air) | 35 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover |
| 5 | Thermal Stability Test (185 mm² Conductor) | 23.4 kA, 2 s, twice, no visible damage |
| 6 | Dynamic Stability Test | 82.6 kA, ≥ 10 ms, no visible damage |
| 7 | Moisture Test (Indoor) | 15 kV, 300 h, no breakdown, no flashover |
| 8 | Salt Spray Test (Outdoor) | 15 kV, 1000 h, no breakdown, no flashover |
Product overview
◆The product is available in single-core, two-core, three-core, four-core, and five-core versions, and has been widely used for low-voltage cable terminations and intermediate connections.
◆Excellent surface hydrophobicity, ensuring the product maintains strong resistance to contamination.
◆Compact size, lightweight, and reliable performance.
◆Application Scope: The product demonstrates excellent cold and heat resistance, making it particularly suitable for high-altitude, cold, humid, salt-spray, and heavily polluted environments.
Installation requires no open flame, making it ideal for flammable and explosive areas such as petroleum, chemical, mining, and tunneling sites.
![]() |
![]() |
![]() |
![]() |
| 12/20 kV Single-Core Cold Shrink Indoor Termination – Installation Drawing | 12/20 kV Three-Core Cold Shrink Outdoor Termination – Installation Drawing | 12/20 kV Three-Core Cold Shrink Outdoor Termination – Supporting Drawing | 12/20 kV Three-Core Cold Shrink Intermediate Connection – Supporting Drawing |
Technical Data - Model Selection
| Product Type | Model | Conductor Cross-section(mm²) |
| 12/20 kV Cold Shrink Indoor Termination | GHD-20HNLS-3(1)*35-500 | 35-500 |
| 12/20 kV Cold Shrink Outdoor Termination | GHD-20HWLS-3(1)*35-500 | 35-500 |
| 12/20 kV Cold Shrink Joint | GHD-20JTLS-3(1)*35-500 | 35-500 |
| 18/20 kV Cold Shrink Indoor Terminationl | GHD-24HNLS-3(1)*35-630 | 35-630 |
| 18/20 kV Cold Shrink Outdoor Termination | GHD-24HWLS-3(1)*35-630 | 35-630 |
| 18/20 kV Cold Shrink Joint | GHD-24JTLS-3(1)*35-630 | 35-630 |