Silicone Cold Shrink Tubing Wrap Grip Protective Sleeve

Power Frequency Withstand Voltage:
54 kV, 5 min, No Breakdown
Partial Discharge Test:
Partial Discharge Magnitude≤ 10 pC at 20 kV
Impulse Voltage Test:
125 kV, 10 positive and 10 negative impulses, no breakdown
Constant Voltage Load Cycling Test (in Air):
35 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
Thermal Stability Test (185 mm² Conductor):
23.4 kA, 2 s, twice, no visible damage
Dynamic Stability Test:
82.6 kA, ≥ 10 ms, no visible damage
Moisture Test (Indoor):
15 kV, 300 h, no breakdown, no flashover
Salt Spray Test (Outdoor):
15 kV, 1000 h, no breakdown, no flashover

 

Medium-voltage electrical infrastructure demands dependable moisture protection and continuous insulation resistance. Hangda manufactures high-grade Cold Shrink Cable Accessories designed for 12/20kV and 18/20kV power distribution networks. Utilizing factory-expanded elastomeric compounds, each silicone cold shrink tube delivers constant radial tension directly over cable joints and terminations without open flames or heat torches.

Moisture Ingress Protection and Mechanical Durability

Outdoor cable joints face ultraviolet radiation, chemical runoff, and severe thermal cycling. Applying a cold shrink wrap creates a resilient active seal that moves with thermal expansion.

  1. Resists tracking and erosion under severe environmental weathering.

  2. Maintains high dielectric strength exceeding 20 kV/mm under continuous operational loads.

  3. Provides hydrophobic surface properties that prevent surface moisture film formation.

Technical Specifications

Parameter Tested Value Standard
Operating Voltage 12/20 kV, 18/20 kV IEC 60502-4
Tensile Strength ≥ 10.5 MPa ASTM D412
Elongation at Break ≥ 750% ASTM D412
Volume Resistivity ≥ 1.0 × 10¹⁴ Ω·cm ASTM D257

Application Procedure and Structural Security

Safe Installation Sequence

Field assembly requires zero specialized tooling, eliminating flame permits inside enclosed vaults.

  1. Position the silicone shrink tubing over the prepared cable core.

  2. Extract the inner supporting spiral core counterclockwise.

  3. Inspect the uniform collar contraction across the entire splice interface.

The elastic cold shrink grip secures cable jackets against mechanical vibration and harsh contaminants.


12/20, 18/20 kV Fully Cold Shrink Three-Core Terminal – Installation Outline Drawing

Silicone Cold Shrink Tubing Wrap Grip Protective Sleeve

Electrical Performance Tests

No. Test Item Standard Requirements
1 Power Frequency Withstand Voltage 54 kV, 5 min, No Breakdown
2 Partial Discharge Test Partial Discharge Magnitude≤ 10 pC at 20 kV
3 Impulse Voltage Test 125 kV, 10 positive and 10 negative impulses, no breakdown
4 Constant Voltage Load Cycling Test (in Air) 35 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
5 Thermal Stability Test (185 mm² Conductor) 23.4 kA, 2 s, twice, no visible damage
6 Dynamic Stability Test 82.6 kA, ≥ 10 ms, no visible damage
7 Moisture Test (Indoor) 15 kV, 300 h, no breakdown, no flashover
8 Salt Spray Test (Outdoor) 15 kV, 1000 h, no breakdown, no flashover

Product overview

◆The product is available in single-core, two-core, three-core, four-core, and five-core versions, and has been widely used for low-voltage cable terminations and intermediate connections.

◆Excellent surface hydrophobicity, ensuring the product maintains strong resistance to contamination.

◆Compact size, lightweight, and reliable performance.

◆Application Scope: The product demonstrates excellent cold and heat resistance, making it particularly suitable for high-altitude, cold, humid, salt-spray, and heavily polluted environments.

Installation requires no open flame, making it ideal for flammable and explosive areas such as petroleum, chemical, mining, and tunneling sites.

Silicone Cold Shrink Tubing Wrap Grip Protective Sleeve Silicone Cold Shrink Tubing Wrap Grip Protective Sleeve Silicone Cold Shrink Tubing Wrap Grip Protective Sleeve Silicone Cold Shrink Tubing Wrap Grip Protective Sleeve
12/20 kV Single-Core Cold Shrink Indoor Termination – Installation Drawing 12/20 kV Three-Core Cold Shrink Outdoor Termination – Installation Drawing 12/20 kV Three-Core Cold Shrink Outdoor Termination – Supporting Drawing 12/20 kV Three-Core Cold Shrink Intermediate Connection – Supporting Drawing

Technical Data - Model Selection

Product  Type Model Conductor Cross-section(mm²)
12/20 kV Cold Shrink Indoor Termination GHD-20HNLS-3(1)*35-500 35-500
12/20 kV Cold Shrink Outdoor Termination GHD-20HWLS-3(1)*35-500 35-500
12/20 kV Cold Shrink Joint GHD-20JTLS-3(1)*35-500 35-500
18/20 kV Cold Shrink Indoor Terminationl GHD-24HNLS-3(1)*35-630 35-630
18/20 kV Cold Shrink Outdoor Termination GHD-24HWLS-3(1)*35-630 35-630
18/20 kV Cold Shrink Joint GHD-24JTLS-3(1)*35-630 35-630

Contact Us

Leave us a message to get a quote

Request a Quote or Technical Support

Leverage our 20+ years of manufacturing experience and joint R&D capabilities. Let us provide you with reliable, high-performance electrical solutions tailored to your project needs.

This site uses cookies

We use cookies to collect information about how you use this site. We use this information to make the website work as well as possible and improve our services.more details

WhatsApp us