Cold Shrink Cable Joint And Abandonment Kit Accessories

Power Frequency Withstand Voltage:
117 kV, 5 min, No Breakdown
Partial Discharge Test:
Partial Discharge Magnitude≤ 10 pC at 45 kV
Impulse Voltage Test:
200 kV, 10 positive and 10 negative impulses, no breakdown
Constant Voltage Load Cycling Test (in Air):
65 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
Moisture Test (Indoor):
32.5 kV, 300 h, no breakdown, no flashover
Salt Spray Test (Outdoor):
32.5 kV, 1000 h, no breakdown, no flashover
DC Withstand Voltage:
104 kV, 15 min, No Breakdown

 

Power distribution networks require dependable insulation and environmental protection in confined spaces where open flames are prohibited. Manufactured from high-grade silicone rubber, cold shrink cable accessories deliver continuous radial pressure around conductors without external heat sources. When circuit lines undergo scheduled maintenance or permanent shutdown, a cable abandonment kit isolates exposed conductor ends against moisture ingress and dielectric degradation.

Radial Pressure and Stress Management

Thermal cycling causes cable insulation to expand and contract repeatedly. A factory-expanded cold shrink cable joint adapts dynamically to these diameter variations, maintaining tight interface contact across heavy load fluctuations.

  1. Flame-free installation: Eliminates torch hazards inside tunnels and petrochemical facilities.

  2. Integrated stress control: Manages electrical stress gradients to inhibit partial discharge.

Technical Characteristics

Specification Standard Rating
Voltage Class 26/35 kV
Material Formulation High-Tear Silicone Rubber
Dielectric Strength ≥ 20 kV/mm
Volume Resistivity ≥ 1.0 × 10¹⁴ Ω·cm
Thermal Range -50°C to +150°C

Environmental Sealing and Submersible Protection

Water penetration remains a primary driver of electrical breakdown in underground conduits. Deploying an elastic cold shrink joint establishes a submersible seal that withstands chemical exposure, ozone attack, and ground movement.

  1. Pull-cord mechanism: Unravels smoothly without specialized mechanical tools.

  2. Hydrophobic outer wall: Repels moisture to prevent tracking resistance failures.

Explore high-quality cold shrink cable accessories to enhance high-voltage infrastructure and maintain network performance.


26/35 kV Fully Cold Shrink Three-Core Terminal – Installation Outline Drawing

Cold Shrink Cable Joint And Abandonment Kit Accessories

Electrical Performance Tests

No. Test Item Standard Requirements
1 Power Frequency Withstand Voltage 117 kV, 5 min, No Breakdown
2 DC Withstand Voltage 104 kV, 15 min, No Breakdown
3 Partial Discharge Test Partial Discharge Magnitude≤ 10 pC at 45 kV
4 Impulse Voltage Test 200 kV, 10 positive and 10 negative impulses, no breakdown
5 Constant Voltage Load Cycling Test (in Air) 65 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
6 Moisture Test (Indoor) 32.5 kV, 300 h, no breakdown, no flashover
7 Salt Spray Test (Outdoor) 32.5 kV, 1000 h, no breakdown, no flashover

Product overview

◆The product is available in single-core, two-core, three-core, four-core, and five-core versions, and has been widely used for low-voltage cable terminations and intermediate connections.

◆Excellent surface hydrophobicity, ensuring the product maintains strong resistance to contamination.

◆Compact size, lightweight, and reliable performance.

◆Application Scope: The product demonstrates excellent cold and heat resistance, making it particularly suitable for high-altitude, cold, humid, salt-spray, and heavily polluted environments.

Installation requires no open flame, making it ideal for flammable and explosive areas such as petroleum, chemical, mining, and tunneling sites.

Cold Shrink Cable Joint And Abandonment Kit Accessories Cold Shrink Cable Joint And Abandonment Kit Accessories Cold Shrink Cable Joint And Abandonment Kit Accessories Cold Shrink Cable Joint And Abandonment Kit Accessories
26/35 kV Single-Core Cold Shrink Outdoor Termination – Installation Drawing 26/35 kV Three-Core Cold Shrink Outdoor Termination – Installation Drawing 26/35 kV Three-Core Cold Shrink Outdoor Termination – Supporting Drawing 26/35 kV Three-Core Cold Shrink Intermediate Connection – Supporting Drawing

Technical Data - Model Selection

Product  Type Model Conductor Cross-section(mm²)
26/35 kV Cold Shrink Indoor Termination GHD-35HNLS-3(1)*50-630 50-630
26/35 kV Cold Shrink Outdoor Termination GHD-35HWLS-3(1)*50-630 50-630
26/35 kV Cold shrink Joint GHD-35JTLS-3(1)*50-630 50-630