Power Frequency Withstand Voltage:
117 kV, 5 min, No Breakdown
Partial Discharge Test:
Partial Discharge Magnitude≤ 10 pC at 45 kV
Impulse Voltage Test:
200 kV, 10 positive and 10 negative impulses, no breakdown
Constant Voltage Load Cycling Test (in Air):
65 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
Moisture Test (Indoor):
32.5 kV, 300 h, no breakdown, no flashover
Salt Spray Test (Outdoor):
32.5 kV, 1000 h, no breakdown, no flashover
DC Withstand Voltage:
104 kV, 15 min, No Breakdown

 

Matching cable dimensions with protective insulation prevents moisture intrusion and electrical flashover in medium-voltage power distribution. In 26-35kV installations, selecting the correct cold shrink sleeve ensures sustained radial pressure over cable sheaths without requiring open flames or specialized heating tools.

Standard Sizing Guidelines for High-Voltage Applications

Selecting appropriate cold shrink tubing sizes requires verifying both the expanded inner diameter and the recovered inner diameter against cable insulation shields.

  1. Outer Diameter Coverage: The minimum cable diameter must exceed the relaxed tube dimension to maintain active sealing.

  2. Core Extraction Clearance: Cable joints require sufficient axial space along the conductor for smooth plastic core unrolling.

Technical Specifications and Dimension Chart

The following specifications outline physical dimensions and insulation parameters for medium-voltage splices:

Conductor Cross-Section (mm²) Cable Sheath Range (mm) Recovered Length (mm) Dielectric Strength (kV/mm)
50 – 95 24 – 34 450 ≥ 20
120 – 185 32 – 43 500 ≥ 20
240 – 400 40 – 54 550 ≥ 20

Reliable Performance with Certified Components

Field Verification Steps

  1. Inspect the cable sheath diameter before stripping insulation layers.

  2. Position the epdm cold shrink tube centrally over the connector.

  3. Pull the supporting plastic ribbon smoothly toward the ground terminal.

Certified Medium-Voltage Cable Solutions

Manufactured from cross-linked synthetic rubber with high tracking resistance, Hangda Cold Shrink Cable Accessories provide dependable weatherproofing and moisture exclusion across harsh operating environments. Hangda pre-expanded assemblies undergo rigorous factory discharge tests to ensure operational safety.


26/35 kV Fully Cold Shrink Three-Core Terminal – Installation Outline Drawing

EPDM Cold Shrink Tubing Sleeve Sizes and Dimensions

Electrical Performance Tests

No. Test Item Standard Requirements
1 Power Frequency Withstand Voltage 117 kV, 5 min, No Breakdown
2 DC Withstand Voltage 104 kV, 15 min, No Breakdown
3 Partial Discharge Test Partial Discharge Magnitude≤ 10 pC at 45 kV
4 Impulse Voltage Test 200 kV, 10 positive and 10 negative impulses, no breakdown
5 Constant Voltage Load Cycling Test (in Air) 65 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
6 Moisture Test (Indoor) 32.5 kV, 300 h, no breakdown, no flashover
7 Salt Spray Test (Outdoor) 32.5 kV, 1000 h, no breakdown, no flashover

Product overview

◆The product is available in single-core, two-core, three-core, four-core, and five-core versions, and has been widely used for low-voltage cable terminations and intermediate connections.

◆Excellent surface hydrophobicity, ensuring the product maintains strong resistance to contamination.

◆Compact size, lightweight, and reliable performance.

◆Application Scope: The product demonstrates excellent cold and heat resistance, making it particularly suitable for high-altitude, cold, humid, salt-spray, and heavily polluted environments.

Installation requires no open flame, making it ideal for flammable and explosive areas such as petroleum, chemical, mining, and tunneling sites.

EPDM Cold Shrink Tubing Sleeve Sizes and Dimensions EPDM Cold Shrink Tubing Sleeve Sizes and Dimensions EPDM Cold Shrink Tubing Sleeve Sizes and Dimensions EPDM Cold Shrink Tubing Sleeve Sizes and Dimensions
26/35 kV Single-Core Cold Shrink Outdoor Termination – Installation Drawing 26/35 kV Three-Core Cold Shrink Outdoor Termination – Installation Drawing 26/35 kV Three-Core Cold Shrink Outdoor Termination – Supporting Drawing 26/35 kV Three-Core Cold Shrink Intermediate Connection – Supporting Drawing

Technical Data - Model Selection

Product  Type Model Conductor Cross-section(mm²)
26/35 kV Cold Shrink Indoor Termination GHD-35HNLS-3(1)*50-630 50-630
26/35 kV Cold Shrink Outdoor Termination GHD-35HWLS-3(1)*50-630 50-630
26/35 kV Cold shrink Joint GHD-35JTLS-3(1)*50-630 50-630

Contact Us

Leave us a message to get a quote

Request a Quote or Technical Support

Leverage our 20+ years of manufacturing experience and joint R&D capabilities. Let us provide you with reliable, high-performance electrical solutions tailored to your project needs.

This site uses cookies

We use cookies to collect information about how you use this site. We use this information to make the website work as well as possible and improve our services.more details

WhatsApp us