EPDM Cold Shrink Electrical Insulation Tape Products

Power Frequency Withstand Voltage:
117 kV, 5 min, No Breakdown
Partial Discharge Test:
Partial Discharge Magnitude≤ 10 pC at 45 kV
Impulse Voltage Test:
200 kV, 10 positive and 10 negative impulses, no breakdown
Constant Voltage Load Cycling Test (in Air):
65 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
Moisture Test (Indoor):
32.5 kV, 300 h, no breakdown, no flashover
Salt Spray Test (Outdoor):
32.5 kV, 1000 h, no breakdown, no flashover
DC Withstand Voltage:
104 kV, 15 min, No Breakdown

 

High-voltage power distribution networks require moisture sealing and continuous radial pressure across cable splices. Hangda delivers high-performance Cold Shrink Cable Accessories manufactured from formulated ethylene propylene diene monomer. Utilizing an epdm cold shrink structure, each assembly contracts over irregular cable profiles upon core removal, securing void-free dielectric insulation without torches.

Core Performance and Field Advantages

Deploying cold shrink electrical tape designs resolves open flame hazards in confined substations and underground trenches.

  1. Constant Radial Active Pressure: Memory-retentive polymers maintain dynamic grip during thermal expansion cycles.

  2. High Dielectric Breakdown Voltage: Exceeds 20 kV/mm to prevent partial discharge events.

  3. Environmental Resistance: Resists ultraviolet rays, ozone exposure, chemical soil immersion, and fungal growth.

Specifications: 26/35kV Cable Systems

Parameter Rating Test Method
Dielectric Strength ≥ 20 kV/mm IEC 60243
Tensile Strength ≥ 10.5 MPa ASTM D412
Elongation at Break ≥ 650% ASTM D412
Volume Resistivity 1.0 × 10¹⁴ Ω·cm ASTM D257
Operational Temperature -40°C to +105°C IEC 60068

Hangda Manufacturing Standards

Elastomeric Compounding

Hangda enforces rigorous factory testing for each electrical cold shrink unit, verifying tracking resistance and stress cone precision before dispatch.

Simplified Cable Jointing Workflow

Field crews execute rapid setups through standard operational protocols:

  1. Clean conductor insulation shields according to specified dimensions.

  2. Position the cool shrink core assembly over the connector junction.

  3. Unwind the supporting spiral plastic core counterclockwise until full contraction occurs.


26/35 kV Fully Cold Shrink Three-Core Terminal – Installation Outline Drawing

EPDM Cold Shrink Electrical Insulation Tape Products

Electrical Performance Tests

No. Test Item Standard Requirements
1 Power Frequency Withstand Voltage 117 kV, 5 min, No Breakdown
2 DC Withstand Voltage 104 kV, 15 min, No Breakdown
3 Partial Discharge Test Partial Discharge Magnitude≤ 10 pC at 45 kV
4 Impulse Voltage Test 200 kV, 10 positive and 10 negative impulses, no breakdown
5 Constant Voltage Load Cycling Test (in Air) 65 kV, conductor temperature 95–100 ℃, total 60 cycles, no breakdown, no flashover
6 Moisture Test (Indoor) 32.5 kV, 300 h, no breakdown, no flashover
7 Salt Spray Test (Outdoor) 32.5 kV, 1000 h, no breakdown, no flashover

Product overview

◆The product is available in single-core, two-core, three-core, four-core, and five-core versions, and has been widely used for low-voltage cable terminations and intermediate connections.

◆Excellent surface hydrophobicity, ensuring the product maintains strong resistance to contamination.

◆Compact size, lightweight, and reliable performance.

◆Application Scope: The product demonstrates excellent cold and heat resistance, making it particularly suitable for high-altitude, cold, humid, salt-spray, and heavily polluted environments.

Installation requires no open flame, making it ideal for flammable and explosive areas such as petroleum, chemical, mining, and tunneling sites.

EPDM Cold Shrink Electrical Insulation Tape Products EPDM Cold Shrink Electrical Insulation Tape Products EPDM Cold Shrink Electrical Insulation Tape Products EPDM Cold Shrink Electrical Insulation Tape Products
26/35 kV Single-Core Cold Shrink Outdoor Termination – Installation Drawing 26/35 kV Three-Core Cold Shrink Outdoor Termination – Installation Drawing 26/35 kV Three-Core Cold Shrink Outdoor Termination – Supporting Drawing 26/35 kV Three-Core Cold Shrink Intermediate Connection – Supporting Drawing

Technical Data - Model Selection

Product  Type Model Conductor Cross-section(mm²)
26/35 kV Cold Shrink Indoor Termination GHD-35HNLS-3(1)*50-630 50-630
26/35 kV Cold Shrink Outdoor Termination GHD-35HWLS-3(1)*50-630 50-630
26/35 kV Cold shrink Joint GHD-35JTLS-3(1)*50-630 50-630