Screw Type Terminal Blocks Losing Contact? Copper Relaxation Explained

Type:
Feed-through terminal block
Nominal Voltage:
800 V
Nominal Current:
57 A
Number Of Connections:
2
Connection Method:
Screw connection
Rated Cross Section:
10 mm²
Cross Section:
0.5 mm² - 16 mm²
Color:
gray

 

When contact resistance rises on a screw type terminal block, check three things first: torque, thermal imaging, and micro-ohm readings. If the screw turns another 2–3 rotations without discoloration, pitting, or stripped threads, treat it as copper relaxation. Replace the terminal only when heat damage or thread failure is visible.

What Copper Relaxation Does

Copper deforms under sustained clamping pressure. This creep runs at a microscopic level for years, shrinking the real contact area between conductor and current bar. The screw relaxes too, dropping axial force with no outside help.

Thermal cycling accelerates both. Copper expands at roughly 17×10⁻⁶ K⁻¹, while steel and brass differ. Each load cycle moves the joint microscopically, settling the contact and opening oxidation paths.

Three-Step Diagnostic Process

  1. De-energize, lock out, and record the original torque value.

  2. Use thermal imaging to locate hot spots, then a micro-ohmmeter for contact resistance.

  3. Re-tighten to the manufacturer's specified torque and mark the rotation angle.

Reference thresholds below, based on IEC 60947-7-1 temperature-rise conventions and industry micro-ohm practice.

Reading Status Action
Below 3.0 mΩ Nominal Continue scheduled monitoring
3.0–10.0 mΩ Warning Re-strip wire, re-insert, re-torque
Above 10.0 mΩ Failure Replace terminal or connection method

Layered Countermeasures

Scheduled torque verification

A calibrated torque audit at commissioning, 72 hours later, then annually catches relaxation before resistance climbs. For main feeders, move to every six months.

Integrated locking mechanisms

Screw clamp type terminals with spring-loaded locking designs hold clamping force as materials relax. The Reakdyn principle used in JHD5 series screw clamp terminal blocks creates a self-locking effect through elastic deformation of the clamping body. This cuts reliance on manual re-tightening across the terminal's service life.

Ferrules on fine-stranded conductors

Bare fine-stranded wire in a screw clamp terminal contacts through a fraction of its cross-section. A crimped ferrule consolidates every strand into one gas-tight cylinder. The screw then clamps a defined, repeatable surface. This applies to any screw terminal fuse block or feed-through block accepting flexible wire.

JHD5-10 Reference Specifications

Parameter Value
Rated cross-section 10 mm²
Screw torque (10 mm²) ~1.2–1.5 N·m
Conductor range 0.75–25 mm²
Locking mechanism Reakdyn spring self-lock
Housing material UL94 V-0 rated

These values align with the product datasheet and IEC 60947-7-1 requirements for copper conductor terminal blocks.

When to Replace Instead

Three conditions mean replacement, not another torque pass:

  • Visible discoloration or charring on the terminal body or insulation

  • Pitted or eroded contact surfaces on the current bar

  • Stripped threads, or a terminal block clamp that no longer retains the conductor

The damage here is metallurgical. A screw clamp terminal block that loosened once in a high-vibration environment will loosen faster after the first event.

Scenario Boundaries

Condition Re-tighten + Ferrules Switch to Spring/Push-in
Low vibration, stable load Sufficient Optional
Continuous vibration Not recommended Required
Thermal cycling above 60°C Monitor closely Required
Visible contact damage Insufficient Required

For panels under continuous vibration or frequent load cycling above 60°C internal temperature, spring-clamp or push-in terminations remove the screw interface from the reliability equation. The deciding factor is whether the clamping mechanism can still generate the contact force the circuit needs.

FAQ

Q: Is copper relaxation the same as a loose screw?

A: No. A loose screw is mechanical. Relaxation is time-dependent deformation of the conductor and screw under sustained pressure and heat.

Q: Must fine-stranded wire use ferrules in screw terminals?

A: Yes. Bare strands splay and make unpredictable contact. A ferrule creates a defined, gas-tight interface.

Q: When must the terminal be replaced?

A: Discoloration, pitting, stripped threads, or resistance above 10 mΩ after re-tightening.


Model Function Wire IEC cross-section Wire UL Thickness Maximum current Number of packages Thickness/Height(Screw Type Terminal Blocks Losing Contact? Copper Relaxation Explained)/Width mm Rated voltage/rated current/rated cross-sectior
JHD5-10 Screw Type Terminal Blocks Losing Contact? Copper Relaxation Explained 10 mm²
6 mm²
10 mm²
6 AWG 10 AWG 6 AWG 10.2 mm 57 A 60 10.2/47/42.5 800 V/57 A/10 mm²

Specfication: 

End cover D2.5-10
Cross-connection 10-Polo,Separable ZL2-10 ZL3-10 ZL10-10
Insertion bridge 10-Polo,Separable BLS2-10 BLS3-10 BLS10-10
Partition plate FP
Small Partition CP
Marking tags ZB10
Screw/Tightening torque(Nm) M4/1.2
Material PA
Flame retardant rating UL-94 V0
Dimensions Screw Type Terminal Blocks Losing Contact? Copper Relaxation Explained

With universal mounting feet for standard top-hat(Ω profile) and G-profile DIN rail mounting.

Contact Us

Leave us a message to get a quote

Request a Quote or Technical Support

Leverage our 20+ years of manufacturing experience and joint R&D capabilities. Let us provide you with reliable, high-performance electrical solutions tailored to your project needs.

This site uses cookies

We use cookies to collect information about how you use this site. We use this information to make the website work as well as possible and improve our services.more details

WhatsApp us