Separable Screened Insulated Cable Connectors
- Rated voltage:
- 15 kV
- Rated current:
- 630 A
- AC Withstand Voltage for 5min:
- 39 kV
- Partial Discharge:
- 15 kV,Q≤10 pC
- Impulse Withstand Voltage(10 times foreach polarity):
- 95 kV
- Screen Resistance:
- ≤5000 Ω
- Reference standards:
- GB/T 12706.4、IEC 60502-4
Medium-voltage electrical distribution demands reliable terminations capable of handling voltage surges and environmental stress. A modern Separable Connector provides a fully shielded, submersible interface for switchgear, transformers, and ring main units. Hangda Electric manufactures these components using high-grade EPDM rubber to ensure complete insulation and touch-safe operation in modern power grids.
Operational Features of Screened Assemblies
Standard distribution networks rely on high-performance Screened separable connectors to maintain continuous grounding and prevent electrical arcing. Hangda incorporates an outer conductive layer that keeps electrical stresses contained within the housing.
-
Shielded design prevents accidental contact during maintenance.
-
Integrated capacitive test points allow quick voltage verification.
-
High-durability EPDM material resists ozone, tracking, and moisture ingress.
Technical Specifications
| Parameter | Specification |
|---|---|
| Rated Voltage | 15 kV / 24 kV |
| Continuous Current | 630 A |
| Material | EPDM Rubber |
| Compliance Standard | IEC 60502-4 / IEEE 386 |
| Discharge Level | < 10 pC at 1.73 U0 |
Grid Protection and Selection
Deploying Separable insulated connectors optimizes compact substation footprints while expanding circuit flexibility. Hangda Electric tests each 15kV plug-in arrester to maintain low partial discharge levels and withstand severe overvoltages.
Application Steps
-
Inspect cable preparation dimensions according to manufacturer standards.
-
Secure the separable cable connector onto the bushing interface using calibrated torque tools.
-
Connect earth wires to complete the conductive shield grounding loop.
Versatile Separable Connectors lower system downtime through simplified disconnection procedures.
Product features
The 630 A rear plug-in cable connector is used in conjunction with the front plug-in cable connector product. It provides branching for 630 A circuits but cannot be directly connected to products such as bushings. Its rear end can be sealed with an insulator or extended to connect another rear plug-in cable connector and rear plug-in arrester.
Utilizing advanced rear injection technology, the outer layer features a semi-conductive shielding layer that is touch-safe, ensuring personal safety. The unique stress cone structure effectively dissipates electric field stress, resolving electric field stress issues at the cut-off point of the cable shielding layer. It offers expandability, flexible installation and removal, and enables T-type cable connections. The product is fully sealed, fully insulated, fully protected, maintenance-free, submersible-resistant, and pollution-resistant.

Technical Data
| Rated voltage | 15 kV | ||
| Rated current | 630 A | ||
| AC withstand voltage (5 min) | 39 kV | ||
| Partial Discharge | 15 kV,Q≤10 pC | ||
| Impulse withstand voltage (± polarity, 10 impulses each) | 95 kV | ||
| Screen Resistance | ≤5000 Ω | ||
| Reference standards:GB/T 12706.4、IEC 60502-4 | |||
Models Selection
| Product model | Cross sectional area nominal(mm²) | 8.7/15 kV Outer Diameter of Cable Insulation(mm²) | ||
| GHD-15/630A-HC-25 | 25 | 16.6 | ||
| GHD-15/630A-HC-35 | 35 | 17.6 | ||
| GHD-15/630A-HC-50 | 50 | 19 | ||
| GHD-15/630A-HC-70 | 70 | 20.6 | ||
| GHD-15/630A-HC-95 | 95 | 22.2 | ||
| GHD-15/630A-HC-120 | 120 | 23.6 | ||
| GHD-15/630A-HC-150 | 150 | 25.2 | ||
| GHD-15/630A-HC-185 | 185 | 26.7 | ||
| GHD-15/630A-HC-240 | 240 | 29 | ||
| GHD-15/630A-HC-300 | 300 | 31.2 | ||
| GHD-15/630A-HC-400 | 400 | 34.4 | ||
| GHD-15/630A-HC-500 | 500 | 38 | ||
Product accessory Illustration